Question
What is the required / recommended temperature range (in Celsius) for the coolant at the inlet to the server's liquid cooling loop for guaranteed operational performance? SYS-422GA-NBRT-LCC

Print
Answer
The requirement for liquid cooling is Max 40C coolant Inlet at Minimum 12 LPM per system.
Was this FAQ helpful?
Enter Comments Below: